The STS Packaged Design Day Tank Series represents a transformation from a build-to-order product to an inventory based product. Based upon over 50 years of experience with day tank systems, beginning with the innovation of the first packaged day tank systems in the 1960’s, Simplex has developed a new design which allows integration of over 150 options into a standard, inventory based package. Likewise, drawings have been transformed to reduce submittal lead times to days. The result is the job-specialized product that owners want with the fit and finish of a standard, high volume product.
|
• | Modular construction to adapt wide ranging requirements to a standard product. |
• | Modular design transforms from build-to-order to inventory based delivery. |
• | 1 week submittal drawings, standard configurations. |
• | Shipment from inventory 5 weeks, standard configurations. |
• | 10-25-60-75-100-150-200-300-400 gallons stock models. Intermediate and larger models available. |
• | UL142 secondary containment (double wall). |
• | UL508A integrated controller. |
• | Freestanding, pad-mountable, indoor (standard) or outdoor (optional). |
• | Integrated single or duplex fill or return pumps 2-25 gpm, .33-1.5 hp. |
• | Backed by Simplex renowned engineering capability and nationwide service. |
Capacities |
10, 25, 60, 75, 100, 150, 200, 300, 400 Gallons |
Product |
Class II Liquid, > 100°F Flash Point |
Control |
UL508A Integrated Controller |
Pumps |
2-25 GPM, 0.33-1.5 HP |
Construction |
UL142 secondary containment tank (double-wall) Suitable for indoor (standard) or outdoor (optional) installation |
Finish |
Simplex Carolina Vermillion (Tank) Simplex Coastal Haze (Controller) |
Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.
Mechanical |
Option 015, Auxiliary Hand Pump, is recommended for installation on all Day Tanks equipped with motor-pumps. The hand pump is used for initial priming of the fuel line from the main tank and as a backup to the motor-pump.
Option 060, 062 Fuel Strainer, is recommended whenever there is a possibility of fuel contamination. Day Tank pumps have extremely close tolerances. Fine abrasives in suspension degrade pumping ability and can jam pump.
In order to assure maintenance of pump prime, one of the following options is recommended for installation on all Day Tanks equipped with motor-pumps: Option 070: Check valve; Option 080, 083: Solenoid valve; or Option 090: Foot valve.
OPT - Description
015 - Auxiliary hand pump, 20 gallons per 100 strokes, 1" NPT (Side mounted)
025 - Locking manual fuel fill cap
060 - Fuel strainer
062 - Duplex strainer
063 - Vent cap
064 - Emergency vent
065 - Drain hand valve
070 - Check valve
080 - Solenoid valve
083 - DC Solenoid Valve
087 - Manual fuel shut-off valve, bronze
088 - Manual fuel shut-off valve, fire-rated
090 - Foot valve
093 - Fusible link valve
095 - Pressure relief valve
100 - Pressure gauge
101 - Vacuum gauge
103 - Flow gauge in line with pump, to 29 GPM
104 - Ball motion flow indicator
105 - Temperature gauge
120 - Extra 1" pipe connection
125 - Extra drop tube
130 - Oversize pipe connections, 1 1/4" to 2 1/2" NPT
131 - Oversize pipe connections, 3” to 6” NPT
140 - Special paint colors
180 - Weatherproof modification
192 - Containment drain hand valve |
Control Devices and Alarms |
OPT - Description
191 - Float switch in rupture basin with alarm (STS standard)
212 - Digital level indicator for local or remote installation
214 - Digital fuel flow indicator
215 - Mechanical dial level gauge
260 - Disconnect switch
261 - System circuit breaker
262 - Control power transformer
265 - Immersion heater
270 - Power available green pilot light
280 - Operation mode selector
285 - Loss of flow alarm
299 - Auxiliary relay
326 - Critical High level cut-out
329 - Low fuel level red light
333 - Critical low fuel alarm
334 - Alarm horn
340 - Running Pump amber light
376 - Manual reset, normally open solenoid valve
377 - Siphon-break solenoid valve
378 - Anti-siphon valve, 2"
383 - Automatic pump-out conversion
390 - Fuel rise pump-out control |
Duplex Pump Systems |
Duplex pump options are used to increase the reliability of a day tank system through the addition of a second, backup pump and level control. In a duplex system, one pump is designated the “lead” pump and the other is the “lag” pump. The lead pump automatically refills the day tank over the tank’s normal operating range of 50% to full. Normally, once the tank has been initially filled, the fuel level should never drop below 50%. Less than 50% is indicative of either a failure of the lead pump or consumption in excess of pump capacity. The lag pump and its separate level controller, acting as a backup senses a drop in fuel level below 50% and starts the lag pump, which then continues to run, along with the lead pump, until the tank is full.
When ordering, remember that duplex systems include two motor-pumps and therefore require a quantity of two of any option related to the motor or pump, such as solenoid valves, strainers, etc.
OPT - Description
345 - Duplex pump controller
346 - Two running time meters
349 - Basic PLC based level and duplex pump controller (replaces analog controller) |
Fuel Oil Coolers (Installed in Return Line) |
OPT - Description
396 - Radiator, fan, motor, flow switch, and control panel, installed and wired on day tank |
Pumps (HP is minimum motor size) |
Series XL Pumps (cast aluminum)
OPT - Description
399 - 2 GPM, 1/3 HP (standard)
404 - 4 GPM, 1/3 HP with lip seal
407 - 7 GPM, 1/2 HP with lip seal
410 - 10 GPM, 3/4 HP with lip seal
417 - 17 GPM, 1 HP with lip seal
425 - 25 GPM, 1 1/2 HP with lip seal
Cast Iron with Lip Seal
OPT - Description
502 - 2 GPM, 1/3 HP
505 - 5 GPM, 1/3 HP
507 - 7 GPM, 3/4 HP
510 - 10 GPM, 1 1/2 HP
515 - 15 GPM, 1 1/2 HP |
Motors |
OPT - Description
600 - 1/3 HP, 115V AC, 1-PH, 60Hz (standard)
605 - 1/3 HP, 230V AC, 1-PH, 60Hz, ODP
615 - 1/3 HP, 110V AC, 1-PH, 50Hz, ODP
616 - 1/3 HP, 220V AC, 1-PH,50Hz, ODP
621 - 1/3 HP, 230/460V AC, 3-PH, ODP, with motor starter
622 - 1/3 HP, 230/460V AC, 3-PH, TEFC, with motor starter
630 - 1/3 HP, 12V DC
635 - 11/3 HP, 24V DC
645 - 1/3 HP, 115V AC, 1-PH, 60Hz, TEFC
700 - 1/2 HP, 115V AC, 1-PH, 60Hz, ODP
705 - 1/2 HP, 230V AC, 1-PH, 60Hz, ODP
715 - 1/2 HP, 110V AC, 1-PH, 50Hz, ODP
716 - 1/2 HP, 220V AC, 1-PH, 50Hz, ODP
721 - 1/2 HP, 230/460V AC, 3-PH, ODP
722 - 1/2 HP, 230/460V AC, 3-PH, TEFC, with motor starter
730 - 1/2 HP, 12V DC
735 - 1/2 HP, 24V DC
745 - 1/2 HP, 230/115V AC, 1-PH, 60Hz, TEFC
822 - 3/4 HP, 230/460V AC, 3-PH, 60Hz, TEFC
825 - 3/4 HP, 230/460V AC, 3-PH, 60Hz, ODP, with motor starter
845 - 3/4 HP, 115/230V AC, 1-PH, 60Hz, TEFC
900 - 1 HP, 115V AC, 1-PH, 60Hz, ODP
905 - 1 HP, 230V AC, 1-PH, 60Hz, ODP
922 - 1 HP, 230/460V AC, 3-PH, 60Hz, TEFC
925 - 1 HP, 230/460V AC, 3-PH, 60Hz, ODP, with motor starter
945 - 1 HP, 115/230V AC, 1-PH, 60Hz, TEFC
1022 - 1 1/2 HP, 230/460V AC, 3-PH, 60Hz, TEFC, with motor starter
1025 - 1 1/2 HP, 230/460V AC, 3-PH, 60Hz, ODP, with motor starter
1045 - 1 1/2 HP, 115/230V AC, 1-PH, 60Hz, TEFC
3-PH motors may be operated at 190/380V; 50Hz. 50Hz operation reduces pump capacity by 5/6.
|
Motor Starters |
OPT - Description
768 - Single phase magnetic motor starter
770 - 3-phase magnetic motor starter
|
Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.
|