Very high capacity electrical loads, for testing, maintenance and performance analysis of large AC power systems can be formed using the Simplex Titan Load Bank. It is a self-contained, semi-portable unit providing resistive and inductive loads to 1500KVA at 0.8 power factor. It can be applied singly or in systems of multiple units paralleled to achieve virtually any total capacity desired. Pictured is a Titan 550 Load Bank.
The Titan is weatherproof and intended for outdoor use. It can be moved using a forklift or a crane, or it can be mounted on a trailer. Trailer installations can accommodate multiple units, within the weight capacity of the trailer.
|
General
Load Elements
• | Simplex Powr-Web chromium alloy, open wire, continuously supported, power resistor. |
• | Elements mounted in slide-out trays. |
• | Resistive and inductive loads controlled separately to permit power factor variation. |
• | Rack mounted inductive load elements. |
• | UL Recognized. |
System Controls
• | Standard: Simplex D-Series Digital Controller with local or remote touchscreen. |
• | Remote operator interface terminal and user programmable automatic test routines. |
Cooling
System Protections
• | Sensors, alarms (alarm message on remote operator interface terminal), lock-outs as appropriate, for the following: fan failure, high exhaust temperature, high intake temperature. |
• | Over temperature switch embedded in coils. |
• | Load Circuit Protection: branch circuit fuses. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system. |
Load Control
• | Branch circuit contactors, each 50KW step. |
• | Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held. |
Connections
• | Control Wiring: 105°C, color coded. |
• | Power Wiring: 150°C XLP color-coded. |
• | Cables connect to full rated copper bus bar with an oversized terminal junction box. |
Enclosure
• | Enclosure abrasively blasted or chemically etched, primed and finished, except exhaust hood which is unpainted, galvanized steel. |
• | Anti-condensation heaters at 120V, 1ø, 240V 1ø, or any common 3ø voltage. |
Capacity |
1500KVA |
Load Type |
Resistive/Inductive |
Power Factor |
0.8 |
Voltages |
All common 3-phase 60 and 50 Hz voltages: 60 Hertz: 208V, 220V, 240V, 416V, 440V, 450V, 460V, 480V, 575V, 600V 50 Hertz: 190V, 200V, 208V, 380V, 400V, 416V |
Frequency |
50, 60 Hz |
Load Steps |
10KW, 7.5 KVAR resolution |
Duty Cycle |
Continuous |
Temperature |
120°F maximum ambient temperature. Exhaust rise: RISE=KW x 3000 / CFM (Note: as airflow is not laminar, exhaust air temperatures are not equal at all points at the plane of air exhaust. Some parcels of air may reach approximately 575°F before mixing. |
Airflow |
Varies by capacities and options selected. |
Fault Rating |
Fuses are rated 200KAIC. The load bank has a 5KAIC short circuit current rating. |
Load Wire Insulation Rating |
600V, 150°C |
Control Wire Insulation Rating |
600V, 105°C |
Fan/Control Power |
Internal, from load bus. Load control circuits and fan motor control operate 120V via transformer. Control circuits are fused. The cooling fan operates at 3-phase line voltage. |
Load Control |
Branch circuit contactors, each 50KW resistive circuit max or each 75KVAR inductive circuit max. Inductdive circuits are double break. Contactors have enclosed silver surfaced contacts, 120V coils (electrically operated and electrically held). |
Element Circuit Protection |
Branch circuit fuses: 50KW each, resistive branch circuit max. 75KVAR inductive branch circuit max. 600V, 200KAIC current limiting type. |
Dimensions |
Varies by capacities and options selected. |
Weight |
Varies by capacities and options selected. |
System Controls
Fan/Control Power
Instrumentation
Malfunction Protections
• | Main load disconnect breaker or fused disconnect switch. |
Load Control
• | Branch circuit contactors each step or each 50 kw circuit maximum. |
• |
Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held. |
Connections
• | Connection via cable in conduit, cable tray, cable duct, bus duct. |
Enclosure
• | Sound attenuation. |
• | Anti-condensation heaters at 120V, 1ø, 240V 1ø, or any common 3ø voltage. |
Highway Trailer
• | Trailer construction conforms to applicable Federal and DOT standards. Includes: safety chains, electric lights, electric brakes, leaf springs, pintle eye coupler, and landing jack. |
Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.
|