The Saturn-HV is a self-contained Load Bank to 15KV utilizing the Simplex Saturn Load Module with on-board dry-type power transformer. It is a freestanding, skidded unit consisting of three principle sections:
1. | High voltage section consisting of main input power terminals, high voltage: 480V 3-phase power transformer, low voltage output terminals, and outputs to load cell. |
2. | 480V, low voltage resistive load section consisting of one 1500KW-3000KW forced air-cooled load cell. |
3. | Control Section. |
|
General
Load Elements
• | Simplex Powr-Web chromium alloy, open wire, continuously supported, power resistor. |
• | Elements mounted in slide-out trays. |
• | UL Recognized |
System Controls
• | Standard: Simplex D-Series Digital Controller with local or remote touchscreen. |
Cooling
• | Integral forced air cooling system. |
• | Ultra-high volume forced air cooling system. |
• | Air temperature rise limited to 150-200°F range. |
• | Vertical airflow -- cold air intake at bottom, hot air exhaust at top. |
• | Water shedding exhaust hood. |
System Protections
• | Sensors, alarms (alarm message on remote operator interface terminal), lock-outs as appropriate, for the following: fan failure, high exhaust temperature and high intake temperature). |
• | Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system. |
Load Control
• | Master load toggle switch and load step toggle switches. |
• | Branch circuit contactors, each 50KW step. |
• | Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held. |
Power
• | Control Wiring: 105°C, color coded. |
• | Power Wiring: 105°C. |
• | Cables connect to full rated copper bus bar with an oversized terminal junction box. |
Enclosure
• | Type 3R weatherproof power section, including load elements and cooling fan. |
• | Type 3R weatherproof control section, thermally and electrically isolated from resistive load power section. |
• | Double wall construction for cool exterior. |
• | Exhaust hood mounts atop power section. Hood may be deleted and a duct flangee provided for indoor application where air is exhausted through a duct to the outdoors. |
• | Service access from three sides via hinged doors with lockable latches. |
• | Enclosure abrasively blasted or chemically etched, primed and finished. |
• | Anti-condensation heaters at 120V, 1ø, 240V 1ø, or any common 3ø voltage. |
Transformer
• | Dry trype transformer |
• | 1500-3000KVA, continuous duty |
• | High voltage delta, 3-wire primary |
• | 480V wy, 4-wire secondary with grounded neutral |
• | 220°C insultation / 150°C rise |
Capacity |
1500KW-3000KW |
Load Type |
Resistive |
Power Factor |
1.0 |
Voltages |
to 15KV AC, 3-phase (typical: 2400V, 3300V, 4160V, 13,200V, 13,800V) Load circuits operate at 480V via main power transformer |
Frequency |
50, 60 Hz |
Load Steps |
50KW resolution |
Duty Cycle |
Continuous |
Temperature |
120°F maximum ambient temperature. Exhaust rise: 150°F - 200°F. Note: As airflow is not laminary, exhaust air temperatures are not equal at all points at the plane of air exhaust. Some parcels of air may reach approximately 575°F before mixing. |
Airflow |
1500KW-2000KW: 45,000 CFM 2100KW-3000KW: 60,000 CFM |
Fault Rating |
Fuses are rated 200KAIC. The load bank has a 5KAIC short circuit current rating. |
Load Wire Insulation Rating |
600V, 150°C |
Control Wire Insulation Rating |
600V, 105°C |
Fan/Control Power |
Internal via high voltage: 480V, 3-phase transformer for fan power. 480:120 transformer for control circuits. |
Dimensions |
Varies by capacities and options selected |
Weight |
Varies by capacities and options selected. |
System Controls
Instrumentation
Enclosure
Transformer
• | Secondary of transformer, connected to output fuse circuit. |
Fan/Control Power
• | External source at customer specified 3-phase voltage. |
Additional Options
• | Primary and / or secondary fused disconnect switch. |
• | Lightning arrestors. |
• | Industrial de-humidifiers. |
Highway Trailer
• | Trailer construction conforms to applicable Federal and DOT standards. Includes: safety chains, electric lights, electric brakes, leaf springs, pintle eye coupler, and landing jack. |
Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.
|