The Simplex Mini-Load Cube R is an ultra-large capacity, fully portable, resistive/reactive Load Bank System intended for field use in testing, maintenance and performance proving of large generating systems.The Load Cube R is rated 1250kw, 937.5kvar at 400-600v commercial AC voltages. The Mini-Load Cube is typically used to test large diesel generators, turbines, paralleled generators and shipboard generators. The Mini-Load Cube utilizes digital load control for direct access of load values, block transitions, and user programmable automation. A selection of digital power meters and data acquisition software is available.
|
Load Elements
System Controls
• | PLC based digital load control. |
• | Remote operator interface terminal and user programmable automatic test routines. |
Cooling
• | Approximately 30,000 CFM. |
• | Power operated intake and exhaust louvers with protective screen. |
• | Forced air cooling with horizontal airflow. |
System Protections
• | Sensors, alarms (alarm message on remote operator interface terminal), lock-outs as appropriate, for the following: fan failure, high exhaust temperature, high intake temperature, high interior temperature (sensed at three points). |
• | Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system. |
Load Control
• | 3-Pole magnetic contactors. |
Connections
• | Control Wiring: 105°C, color coded. |
• | Power Wiring: 150°C XLP color-coded. |
Power
• | Control Wiring: connection to plug-in connectors located within recessed side well. |
• | Control Power Supply: Dual voltage control power transformer with supply power switchable to internal (generator) or external. |
• | Power cable connection behind hinge-up door. Cables connect to full rated copper bus bar. |
Enclosure
• | Type 3R weatherproof construction suitable for all-weather transport and use. |
• | Portable, self-contained: lifting eyes, forklift channels, heavy skid base, and suitable for direct transport by standard flat bed truck. |
• | Four-sided service access via hinged doors with lockable, flush latches. |
Load Type |
Reactive / Resistive |
Capacity |
1563KVA, 1250KW Resistive, 937.5KVAR Inductive |
Power Factor |
0.8 |
Voltages |
480v, 600v, 690v |
Frequency |
50, 60 Hz |
Load Steps |
5KW, 3.75KVAR |
Load Connection |
Cam-Type
|
Load Control |
Manual toggle switches / Remote operator interface terminal and user programmable automatic test routines
|
Cooling Airflow |
Horizontal, 30,000 CFM |
Fan/Control Power |
Internal, from load bus. Load control circuits and fan motor control operate 120V via transformer. Control circuits are fused. The cooling fan operates at 3-phase line voltage. |
Duty Cycle |
Continuous |
Portability |
Fork lift channels, trailerable |
Weight |
12,500 lbs |
Dimensions |
96.5″W x 108″H x 74″D |
Networkable |
Yes |
Outdoor Suitable |
Yes |
|