The Simplex Solar-5 is a very large capacity, resistive/inductive portable load bank capable of 0.8 power factor loads to 5.0MVA (4.0MW, 3.0MVAR). The Solar-5 is designed for low voltage application to 690vAC. PLC based digital load control with touchscreen operator interface is standard. The unit is network capable with other Solar Load Banks as well as most standard Simplex Load Banks in order to form large, ultra high capacity systems which can be controlled from a single operator interface with totalized data acquisition.
|
General
• | The Load Bank is a completely self-contained, freestanding unit which includes all load elements, load control devices, load element branch circuit fuse protection, main load bus and terminals, cooling system, control power supply, digital controller with data acquisition and malfunction detection system and weatherproof enclosure. |
Resistive Load Elements
• | Simplex Powr Web: Open wire, helically wound, chromium alloy, load element thermally derated to 60%. 5% tolerance, 2% balance. .995 p.f. Element wire mechanically supported over entire length such that if a wire should break, the broken wire segments will not short to adjacent conductors or to ground. UL Recognized |
Inductive Load Elements
• | Iron-core, non-saturable air-gap type, with aluminum windings, varnish/epoxy coated. 150°C rise. 220°C insulation |
Load Control
• | Branch circuit contactors, each 50 KW resistive circuit max, each 75 KVAR inductive circuit max. Contactors have enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held. Contactors are IEC type
|
Element Circuit Protection
• | Branch circuit fuses, each 50KW resistive branch circuit max, 75KVAR inductive circuit maximum, 600v, 200kAIC, current limiting type. |
Power Wiring
• | 150°C insulated; color-coded and numbered. |
Control Wiring
Power Connection
• | Plated copper bus bar for bolt-on cable connections, behind hinged door and Cam-Lock style plug-in connectors, bulkhead mounted behind hinged door. 400A, 4/0 connectors. |
Cooling
• | Forced air, vertical airflow, top exhaust. 3 x 15HP, 3-phase, TEFC motor direct driving cast aluminum fan blades. Circuit breaker combination motor starters. Electrically powered exhaust louvers, via linear actuator, with position indicating output. Manual air intake doors with door limit switches |
System Protection
• | Sensors, alarms, lock-outs as appropriate, for the following: Fan Failure, High Exhaust Temperature, High Intake Temperature, Exhaust Louver Open/Closed, Each Louver, Intake Door Open Closed, Access Door Open, Each Door, Fan Motor Overload, and Emergency Stop. |
Enclosure
• | Purpose-built, container style steel enclosure with ISO 20’ container dimensions, corner locking pins. Outdoor weatherproof. Painted dark grey polyurethane over epoxy primer. |
Load Type |
Resistive/Inductive |
Capacity |
5.0MVA 0.8 power factor, 4.0MW resistive, 3.0MVAR inductive |
Voltages |
Low voltage to 690vAC |
Frequency |
50, 60 Hz |
Load Steps |
5KW / 3.75KVAR digital load step resolution |
Load Connection |
Plated copper bus bar for bolt-on cable connections, behind hinged door and Cam-Lock style plug-in connectors, bulkhead mounted behind hinged door. 400A, 4/0 connectors.
|
Load Control |
Digital touch-screen, movable via cable tether
|
Cooling Airflow |
Vertical, Approx 75,000 CFM |
Control Power |
Selectable internal or external. External power requirements: 3 x 15HP cooling fan motors |
Control Power Load |
10.0 KVA |
Duty Cycle |
Continuous |
Portability |
Fork lift channels, lift eyes, trailer mountable |
Enclosure |
Purpose-built, container style steel enclosure with ISO 20’ container dimensions, corner locking pins. Outdoor weatherproof. Painted dark grey polyurethane over epoxy primer. |
Dimensions |
240″W x 100″H x 96″D |
Networkable |
Yes |
Outdoor Suitable |
Yes |
|