Page 84 - Load Bank Rentals
P. 84
Atlantis-500R ®
Water-Cooled Load Bank
Insight Onsite
Dimensions and Key Features
SPECIFICATIONS
CAPACITY: 500KW, Resistive, 1.0 p.f.
VOLTAGE: Low voltage to 600V, specify
FREQUENCY: 50Hz, 60Hz and 400Hz
LOAD STEPS: 50KW resolution standard. 1-5-10-25KW resolution available.
COOLANT: Chiller, city water, closed -loop heat exchanger, natural water (river, lake, etc.)
COOLING: Normal Duty: 10 GPM per 100KW, 62.5°F rise
Minimum Cooling Requirements: 6.25 GPM per 100KW, 100°F rise, outlet not to exceed 170°F
Typical Duty, Chilled Water Systems, 50 GPM per 100KW, 12.5°F rise
Coolant Requirements:
KW = GPM x Temp. Rise (F) x .16, GPM = KW / (Temp. Rise x .16)
Temp. Rise (F) = KW / (GPM x .16)
Particles must be less than 150 microns or a filter is required
PRESSURE DROP: 5 PSI or less
CONTROL POWER: Internal or external source, transformer isolated, 120V
PRESSURE: 180 PSI test pressure, 50 PSI nominal / operating pressure
DUTY CYCLE: Continuous