Page 21 - Load Bank Rentals
P. 21
*
dynaMITE 400R
400KW Digital Load Bank
with Data Acquisition
Overview
• High capacity, 400kw
• Dual voltage: 208-240/416-480vAC
• Digital load control, 5 kw resolution
• Touchscreen operator interface
• Data acquisition and recording
• Network units to form large systems
Description
The Simplex dynaMITE is a large
capacity, high performance Portable
Load Bank designed to provide the
manufacturers, distributors and users of
large AC generators and UPS systems
with sophisticated testing capability.
dynaMITE Load Banks feature digital
controllers with network control and data
acquisition capability. Operator interface
is via touchscreen. Load control is via
screen keypad. All electrical values
display on the screen and are recorded Rental Duty
by the system for future data retrieval. Dual-Voltage Load Bank
Any number of dynaMITE and Electra 208-240/416-480v
Load Banks can be combined for large
system capacities and networked for
central control and data acquisition.
The dynaMITE is rated 400kw of
resistive load at both 240V and 480V,
3-phase. It can be applied at any
AC voltage to 480V AC, 50-60 Hertz
standard, single or 3-phase. Load step
resolution is 5KW.
Features
UL/CUL Listed
Digital Control: PLC based control with
8-inch color TFT touchscreen interface.
MODBUS over RS-485 network Load Element Circuit Protection: Control Power Supply: Dual voltage
communication. See page 3. Branch circuit fuses. One set of fuses control power transformer with supply
each 50KW branch. Fuses are current power switchable to internal (generator)
Instrumentation: Digital power limiting type, 200KAIC, 600V. or external.
transducer with Ethernet communication
to digital controller. Data display on Cooling System: 3-phase, direct-drive Touch Screen: Easily removable from
touchscreen. Data acquisition and fan, 10,500 CFM. panel.
recording. See page 3.
Malfunction Detection System: Connection: Cam-Type power
Load Elements: Simplex “Powr-Web” Protection against fan failure, high connections.
chromium alloy, open wire, continuously exhaust air temperature, high intake
supported, power resistor. air temperature, overvoltage and fan
reversal. Exhaust air temperature
Load Control: 3-Pole contactors. displays on screen. LISTED