Page 93 - Load Bank Rentals
P. 93
Auto Test Software
Automated Generator Load Testing,
Performance-Proving and Documentation
Sample Report
Test Information
Thursday, November
Test Date: Engineer: John Smith Bay: Load Test Bay 1
17, 2011
Customer: Acme Job #: 12345-67-89
Genset
Model: abc123 Series: 123
Rating
kW: 300.00 kVA: 400.00 Volts L-N: 277.00
Volts L-L: 480.00 Amps: 480.00 PF: 0.800
Phase: 3 Hz: 60.00 RPM: 1800.00
Engine
Manufacturer: ABC123 Serial #: 98765-43-21 Model: 123456
Fuel Type: Diesel Governor: DEF456 Controller: HIJ789
Generator
Manufacturer: Marathon Electric Serial #: 654321 Model: 123
Connection: Delta Wires: Other Leads: 3
Test Settings
Transients
Voltage Max + Deviation: 15.00% Frequency Max + Deviation: 15.00%
Voltage Max - Deviation: -5.00% Frequency Max - Deviation: -5.00%
Voltage Dip Recovery Time: 5.00 sec. Frequency Dip Recovery Time: 5.00 sec.
Voltage Rise Recovery Time: 5.00 sec. Frequency Rise Recovery Time: 5.00 sec.
Steady State
Voltage Max + Deviation: 2.00% Frequency Max + Deviation: 0.50%
Voltage Max - Deviation: -2.00% Frequency Max - Deviation: -0.50%