TITAN-600R                                                                                                 ®

        750KVA, 0.8 P.F. Load Bank
                                                                                                     Insight     Onsite



                                            Principle Systems

                                            The Load Bank is a completely self-contained, freestanding unit which includes all
                                            load elements, load control devices, load element branch circuit fuse protection, main
                                            load bus and terminals, cooling system, control power supply, digital controller with
                                            data acquisition and  malfunction detection system and weatherproof enclosure.
                                            Resistive Load Elements: Simplex Powr Web: Open wire, helically wound,
                                            chromium alloy, load element thermally derated to 60%. 5% tolerance, 2% balance.
                                            .995 p.f. Element wire mechanically supported over entire length such that if a wire
                                            should break, the broken wire segments will not short to adjacent conductors or to
                                            ground. UL Recognized
                                            Inductive Load Elements: Iron-core, non-saturable air-gap type, with aluminum
                                            windings, varnish/epoxy coated. 150C rise. 220C insulation
                                            Load Control: Branch circuit contactors, each 50 KW resistive circuit max, each 75
                                            KVAR inductive circuit max. Contactors have enclosed silver surfaced contacts, 120V
                                            coils; electrically operated and electrically held.
                                            Element Circuit Protection: Branch circuit fuses, each 50KW resistive branch circuit
                                            max, 75KVAR inductive circuit max.  , 600v, 200kAIC, current limiting type.

                                            Power Wiring: 150°C insulated; color-coded and numbered.
                                            Control Wiring: 105°C numbered
                                            Power Connection: Cam-Lock style plug-in connectors, bulkhead mounted behind
                                            hinged door. 400A, 4/0 connectors.

                                            Cooling: Forced air, vertical airflow, top exhaust.  2 x 5HP, 3-phase, TEFC motor
                                            direct driving cast aluminum fan blades. Circuit breaker combination motor starters.
                                            Electrically powered exhaust louvers, via linear actuator, with position indicating
                                            output. Manual air intake doors with door limit switches

                                            System Protection: Sensors, alarms, lock-outs as appropriate, for the following: Fan
                                            Failure, High Exhaust Temperature, High Intake Temperature, Exhaust Louver Open/
                                            Closed, Intake Door Open/Closed




























                                            Resistive Elements              Inductive Elements