Page 5 - Load Bank Rentals
P. 5

Fundamentals

                                                                                        of Load Bank Rentals





            Sizing and Running Cables           Heat and Airflow                    Safety
            Rental cables listed in this catalog should be   The user needs to appreciate how hot a load   Load banks are not inherently dangerous but
            operated at approximately 85% maximum of   bank gets and how much hot air is produced.   there are dangers that exist with operation
            their open air current rating. Ampere ratings   As a guide, temp rise (F) = KW x 3000/CFM.    of load banks. This is a technical, industrial
            listed are the NEC free air ratings. Cables   Load banks are heat producing devices   product and should only be set-up and
            listed are suitable for wet or dry aboveground   and must be ventilated. Observe the CFM   operated by trained, technical personnel
            use and should be run in a well ventilated   capacity of the load bank and be certain that   who are specifically authorized by the renter.
            area. Keep cable splice points out of water.   equivalent air intake is provided. If operated   Be certain that all equipment is properly
            3-phase cables must be of absolutely equal   indoors, be cautious to prevent recirculation   grounded. Carefully check cables for wear
            length, especially when multiple cables   of exhaust air and observe ambient   and tear, insulation damage. Check all cam-
            are run per phase. Run 3-phase cables   temperatures. Do not operate vertical airflow   lock connectors that connections are made
            in 3-phase groupings, ideally arrayed in a   load banks under a close ceiling. Maintain a   sound and tight including both connector
            triangle, but at least side-by-side. Never   max ambient of no more than 125°F. Load   mating (the connector twist-tightens) and
            separate phases into A-B-C clusters as this   banks greater than 110kw (Powerstar 110)   the cable within the connector. Be certain
            can lead to electromagnetically induced   are ideally operated outdoors and extreme   that cables are phased correctly. A circuit
            current imbalances, voltage drops and cable   caution should be exercised in the 100-700kw   breaker or fuse set is required at the power
            overheating.                        range. Above 700kw, an indoor space would   source sized appropriately for the conductor
                                                have to be voluminous and well ventilated.   run. Be sure to run adequate ampacity
            Ground Cables                       Indoors, note the presence of sprinkler heads   of cables. Check that generator voltage
            Run at least 33% ground capacity. Connect   as the load bank WILL ACTIVATE sprinklers   corresponds to load bank voltage. Check
            ground cables to ground terminals or ground   very quickly. Outdoors, be observant of   correct airflow direction and if it is necessary
            bar in the load bank. Connect the other end   adjacent equipment, buildings, plantings.   to reverse cooling fan direction, allow fan to
            to the generator ground. Be sure that the   Operate in an area with clear sky above.   fully stop before reversing. Provide the CFM
            generator is solidly grounded to earth ground.   Avoid putting the load bank in a virtual pit   required at an ambient not to exceed 125°F.
            Avoid multiple earth grounds as this can lead   by surrounding it with tall walls or buildings.   Be observant of airflow restrictions and
            to potential differences among the ground   Space multiple load banks 4-6 feet apart,   recirculation of airflow. Be careful that foreign
            points with resultant circulating ground   greater with larger units.   objects are not drawn into cooling intakes.
            currents.                                                               Do not operate indoor load banks in the rain.
                                                                                    Observe common and accepted practices
                                                                                    when operated high voltage electrical
                                                                                    equipment. Note that load bank exterior,
                                                                                    exhaust screens and other sheet metal parts
                                                                                    can be very hot. Wear hearing protection as
                                                                                    required.
















            Rental Load Bank Considerations

            1. Capacity required for the test: KW,   5. Control requirements: local/remote,
              power factor, Voltage               manual/automatic
            2. Rental Load Bank System          6. Data acquisition requirements
              Architecture: one unit or multiple   7. Connection cable requirements
              networked units
            3. Site conditions for the test: indoor/  8. Technician/operator requirements
              outdoor, ventilation and access   9. Other accessories needed
              limitations, environmental conditions
            4. Duration of test, if system is to remain
              set-up for long periods






            © 2021 Simplex, Inc.  All Rights Reserved.  SIMPLEX INC.
            Printed in the USA  •  2103-02.00  •  Page 5  5300 Rising Moon Road, Springfield, IL 62711 • simplexdirect.com • 800-637-8603
            Design subject to change without notice.  Nationwide Manufacturing (ISO9001: 2015 certified)
   1   2   3   4   5   6   7   8   9   10