Page 34 - Load Bank Rentals
P. 34

Trident 1250-R                                                                                             ®

        Digital Load Bank with Data Acquisition
        Rental Duty 600KW - 1250KW                                                                   Insight     Onsite





























        Capacity Detail
                                              FLA                                 KW DETAIL
         Model         KW (1.0pf)      240V         480V       240V/480V    208/416V       380V      240V, 1-ph*
         Trident 600      600          1444         722          600          450          376          300
         Trident 750      750          1806         903          750          563          470          300

         Trident 800      800          1926         963          800          600          500          300
         Trident 900      900          2166         1083         900          675          564          300
         Trident 1000     1000         2406         1203         1000         750          627          300
         Trident 1250     1250         3008         1504         1250         938          783          300

        *Requires external 3-phase fan/control power. Capacity limited to 1250 FLA.

        Voltage: Dual Voltage: 240/480V AC,   Airflow:  21,000 CFM              Digital Load Control
        3-phase Operational at any voltage to
        480V AC maximum, single or 3-phase  Temperature Rise:  180°F nominal    Nominal 5.0 kw resolution: direct enter
        Optional Voltages: Instead of 240/480v   Control/Fan Power:             any load value and controller will apply
        dual voltage:                       •  230/460V, 3-phase, 60 Hertz      load within nominal 5kw resolution
        a. Any 50hz or 60hz single voltage to 690v  •  190/380V, 3-phase, 50 Hertz  Digital Load Calibration
        b. 600v, single voltage             •  Switchable internal (generator)-   Versus Voltage
        c. 600/480v, dual voltage             external
        d. 600/300v, dual voltage           •  External fan/control power       Controller automatically calibrates loads
        e. 480/416v, dual voltage             requirements: 240/480vAC, 3-phase,   for reduced voltage operation.
                                              60 Hertz, 40 / 20  amps service
        f.  208/416v, dual voltage            (7.5HP motor)
        Frequency: 50, 60 Hertz standard    •  230/460-115V control power
                                              transformer internal to Load Bank.
        Connection: 3-wire plus ground
                                            Net Weight:  Approx. 9500 lbs.,
        Time Rating:  Continuous            including load module, trailer, three
        Ambient Air Temperature:  120°F max  reels, 2000’ 4/0 cable, cam-lock style
                                            connectors




        SIMPLEX INC.                                                               © 2021 Simplex, Inc.  All Rights Reserved.
        5300 Rising Moon Road, Springfield, IL 62711 • simplexdirect.com • 800-637-8603  Printed in the USA  •  2103-02.00  •  Page 34
        Nationwide Manufacturing (ISO9001: 2015 certified)                         Design subject to change without notice.
   29   30   31   32   33   34   35   36   37   38   39