Page 27 - Load Bank Rentals
P. 27

MERLIN 500R

                                                                               500KW Resistive Load Bank






                                 KW, 1.0 P.F.             COOLING FAN            LOAD STEPS
             Model            416/480V, 3-phase   HP         Voltage       CFM   KW @ 416/480V, 3-phase

             Merlin 500R            500           3.0     416/480V, 3-ph.  8000  5, 10, 10, 25, 50, 100, 100, 100, 100









































            Fan/Control Power                   Voltage                             Temperature Rating
            User selectable, internal/external  High/Low Mode, operator selectable  125° F max intake air temp
                                                416/480v, 3-ph                      Nominal 110° F rise
            Internal Power
                                                Frequency                           Power Connection
            416-480V, 3-ph, 3-wire, 60Hz
                                                60Hz                                Cam-Type Connector
                                                                                    Qty 3 400A rated 4/0 per pahase
            External Power                                                          Qty 1 4/0 ground
                                                Duty Cycle
            230/460V, 3-ph, 50/60Hz, 20A
                                                Continuous












            © 2021 Simplex, Inc.  All Rights Reserved.  SIMPLEX INC.
            Printed in the USA  •  2103-02.00  •  Page 27  5300 Rising Moon Road, Springfield, IL 62711 • simplexdirect.com • 800-637-8603
            Design subject to change without notice.  Nationwide Manufacturing (ISO9001: 2015 certified)