Trident

Overview

Very-high capacity load testing of generators or electric dynamometer testing of large engines and turbines is achieved with the Simplex Trident Load Bank. The unit capacity range of the Trident is 150KW-1250KW, resistive, unity power factor. The Trident may be used singly or in systems of multiple units which yield total capacities of tens or hundreds of megawatts. Pictured is a 2000KW system (two Tridents) with customer specified paint. Reactive units (inductive or capacitive) are also available.

The Trident is a single or dual voltage Load Bank suitable for all common 50-60-400 hertz voltages up to 600V.

We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.

Features

General

Load Elements

  • Elements mounted in easily accessible, slide out trays.
  • Simplex Powr-Web chromium alloy, open wire, continuously supported, power resistor.
  • UL Recognized.

System Controls

  • Standard: Simplex D-Series Digital Controller with local or remote touchscreen.

Cooling

Malfunction Protections

  • Sensors, alarms (alarm messages and exhaust temperature displays on touchscreen), lockouts as appropriate, for the following: fan failure, high exhaust temperature and high intake temperature.
  • Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system.

Load Control

  • Branch circuit contactors each step or each 50KW circuit maximum.
  • Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.

Connections

  • Control Wiring: 105°C, color coded.
  • Power Wiring: 150°C XLP color-coded.
  • Cables connect to full rated copper bus bar with an oversized terminal junction box.
  • Cables connectable through top or bottom of chassis.

Enclosure

  • Type 3R weatherproof power section, including load elements and cooling fan.
  • Type 3R weatherproof control section, thermally and electrically isolated from resistive load power section.
  • Double wall construction for cool exterior.
  • Service access from three sides via hinged doors with lockable latches.
  • Finish painted with a UL Listed process consisting of either a powder-coated finish or a liquid-coated finish consisting of an epoxy primer and a polyurethane finish.

Specifications

Capacity150KW-1250KW
Load TypeResistive
Power Factor1.0
VoltagesAll common 3-phase
60 and 50 Hz voltages:
60 Hertz: 208V, 220V, 240V, 416V, 440V, 450V, 460V, 480V, 575V, 600V
50 Hertz: 190V, 200V, 208V, 380V, 400V, 416V
Frequency50-60-400 Hz
Load Steps50KW resolution
Duty CycleContinuous
Temperature120°F maximum ambient temperature.
Exhaust rise: RISE=KW x 3000 / CFM (Note: as airflow is not laminar, exhaust air temperatures are not equal at all points at the plane of air exhaust. Some parcels of air may reach approximately 575°F before mixing.
Fault RatingFuses are rated 200KAIC. The load bank has a 5KAIC short circuit current rating.
Load Wire Insulation Rating600V, 150°C
Control Wire Insulation Rating600V, 105°C
Airflow20,000 CFM, 7.5 HP
Fan/Control PowerInternal, from load bus.
Load control circuits and fan motor control operate 120V via transformer. Control circuits are fused.
The cooling fan operaters at 3-phase line voltage.
Dimensions126"W x 48.7"H x 47"D
Weight3,000 lbs

Note: Dimensions and weights are subject to change with capacities and options selected.

Options

System Controls

Fan/Control Power

  • External.

Instrumentation

Malfunction Protections

  • Main load disconnect breaker or fused disconnect switch.

Load Control

  • Branch circuit contactors each step or each 50-kw circuit maximum.
  • Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.

Highway Trailer

  • Trailer construction conforms to applicable Federal and DOT standards. Includes: safety chains, electric lights, electric brakes, leaf springs, pintle eye coupler, and landing jack.

Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.

This website stores cookies on your computer. These cookies are used to collect information about how you interact with our website and allow us to remember you. We use this information in order to improve and customize your browsing experience and for analytics and metrics about our visitors both on this website and other media. To find out more about the cookies we use, see our Privacy Policy.