Nautilus

Overview

The Nautilus is designed expressly for data-center chiller commissioning and testing applications. The Nautilus-250 is a compact, portable product featuring infinite power and water flow control for precise temperature rise setting versus applied power. The Nautilus is fully networkable for control of single or multiple units from a remote station.

Using a PLC with touchscreen HMI, integrated with temperature sensors and flow transducers and controlling an electrically operated water proportioning valve, the Nautilus allows the operator to select precise power levels, versus water temperature rise versus water flow rates. Power level is infinitely controllable over a 0-250kw range.

We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.

Features

General

  • The load bank is a completely self-contained, freestanding unit, which includes all resistive load elements, load control, load element branch circuit fuse protection, main load bus and terminals, valves and fittings, control power supply, malfunction detection system.

Control System

  • PLC control with 8-inch color TFT touchscreen HMI. Screen is configured for local or remote operation. Remote requires 120v power source.

Control Function

  • Master control on-off button; keypad entry of load values, apply and remove buttons; controller calculates reduced voltage load values automatically, applying actual requested load value for the applied voltage up to the reduced voltage capacity of the load bank. Water Flow Control: Either full on or thermostatic control. Thermostatic control is either manual or to a temperature rise preset. Operator interface is a screen based vernier valve control with displays of valve position, flow rate, temp in, temp out, temp rise. Automatic thermostatic control allows operator to enter value of temp rise. Controller then adjusts flow rate to maintain that rise. Controller inhibits over temperature, greater than 180°F outlet temp. Displays: AC 3-phase voltage and current, frequency, kilowatts. Alarms: high outlet temp, low flow, high pressure Messages: normal operation, valve open, valve closed. Water Flow Control Messages: water inlet temp, water outlet temp, overall temp rise, main manifold water flow rate, valve position in percent of open.

Load Cell

  • 1 x 250 kW load, consisting of heavy-gauge, steel housing, load elements, control valves and sensors as described below

Load Elements

  • Immersion type, tubular construction, stainless steel or Incolloy sheathed, chromium-alloy conductor. Screw-plug mounting.

Load Control

  • Triac and Branch circuit contactors, each 25 kw or 50 kW circuit.

Element Circuit Protection

  • Branch circuit fuses, each 50-kW branch circuit or each step.

Power Wiring

  • 150°C insulated; color-coded and numbered, XLP insulation

Control Wiring

  • 90°C, color-coded and numbered.

Power Connection

  • Cam-Type connectors, 1 x 4/0 (400A) per phase and 1 x ground. Bulk-head mount connectors installed on front.

System Protection

  • Sensors: Protection for High water temperature; Low water flow; High pressure. Alarm and shutdown upon failure detection

Sensors

  • Main manifold flow transducer, 4-20mA; inlet water temp thermocouple, exhaust water temp thermocouple; cell pressure.

Enclosure

  • Type 1 indoor freestanding. Approx 24” W x 72” H x 36” D.

Water Flow Control

  • Equipped with main inlet and outlet shutoff ball valves, pressure relief valve. Motorized gate valve on inlet for water flow control.

Specifications

Capacity 250KW
Load Type Resistive
Power Factor 1.0
Voltages 480V AC, 3‑phase, 3‑wire
Frequency 60 Hz
Load Steps Infinitely variable via digital control
Duty Cycle Continuous
Ambient Temperature 52°C
Control Power External, via power inlet and power cord to 120V 15A outlet
Cooling Requirements Fresh water; Nominal 125 GPM supply yields approx. 12.5°F rise at full power; Flow rate is infinitely variable to a max temp rise not to exceed 180°F outlet.
KW = GPM x Temp. Rise (F) x 0.16
GPM = KW / (Temp. Rise x 0.16)
Temp. Rise (F) = KW / (GPM x 0.16)
Weight Approximately 1600 lbs full of water, 900 lbs dry
Water Connection 2‑inch water inlet and outlet with quick disconnect couplings and shutoff ball valves
Enclosure Environmental type 1 freestanding, indoor, portable enclosure. Aluminum frame clad with aluminum panels and doors. Front power connections, rear water connections, casters, forklift pads, lifting eyes. Powder coated white cabinet with blue doors. Dimensions: 72"H x 24"W x 36"D

Options

  • Software for control from a Windows- based PC, for data acquisition and for full testing automation

This website stores cookies on your computer. These cookies are used to collect information about how you interact with our website and allow us to remember you. We use this information in order to improve and customize your browsing experience and for analytics and metrics about our visitors both on this website and other media. To find out more about the cookies we use, see our Privacy Policy.