Vector

Overview

Vector load banks are radiator air cooled units designed for rooftop mounting on enclosed generator sets which have an air turning plenum to exhaust air vertically, through the roof. The Vector load bank mounts over the air exhaust opening and is cooled by the radiator air outflow. Typically, the control section of the load bank overhangs the front of the generator set enclosure, allowing bottom conduit entry. They are fully weatherproof and intended for outdoor installation and operation in all weather conditions. Vector Load Banks are UL/CUL Listed.

Vector load banks are available in a plain galvanized finish or powder-coated to match the generator set enclosure.

We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.

Features

General

  • Standardized, modular construction for quick delivery.
UL Listedd

Load Elements

  • Utilizes the UL Recognized Simplex Powr-Rod element.

System Controls

  • Given the rooftop mounting of the Vector Load Bank, remote operator controls are included for installation in a user convenient location.
  • Manual or automatic, analog or digital controllers. Automatic options include automatic load regulating, automatic exercise, and regenerative power control.
  • Control compartments thermally insulated from load elements.

Cooling

  • Utilizes the air outflow of an engine radiator.

Malfunction Protections

  • Cooling failure sensors lock out load application.
  • Load Circuit Protection: branch circuit fuses. One set of fuses each 50KW branch. Fuses are current limiting type, 200,000 AIC, 600V, enabling safe use on large generating or UPS system.

Load Control

  • Branch circuit contactors each step or each 50KW circuit maximum.
  • Contactors with enclosed silver surfaced contacts, 120V coils; electrically operated and electrically held.

Connections

  • Control Wiring: 105°C, color coded.
  • Power Wiring: 150°C XLP color-coded.
  • Cables connect to full rated copper bus bar with an oversized terminal junction box.

Enclosure

  • Galvanized steel construction. Galvanized finish or powder-coated to match the generator set enclosure.
  • Standard dimensions up to 60" length and width. Lengths or widths over 80" require welded heavy gauge sheet steel construction.
  • Service access panels.

Specifications

Capacity 5-400KW
Load Type Resistive
Power Factor 1.0
Voltages All common 3‑phase
60 and 50 Hz voltages:
60 Hertz: 208V, 220V, 240V, 416V, 440V, 450V, 460V, 480V, 575V, 600V
50 Hertz: 190V, 200V, 208V, 380V, 400V, 416V
Frequency 50‑60‑400 Hz
Load Steps Varies by voltage and KW rating, typically 25KW or 50KW resolution
Duty Cycle Continuous
Temperature Exhaust rise: RISE = KW x 3000 / CFM
(Note: as airflow is not laminar, exhaust air temperatures are not equal at all points at the plane of air exhaust. Some parcels of air may reach approximately 575°F before mixing.)
Airflow Radiator.
Control Power Internal, from load bus.
Load control circuits operate 120V via transformer. Control circuits are fused.
Dimensions Varies by capacities and options selected.
Weight Varies by capacities and options selected.

Options

System Controls

Enclosure

  • Powder-coating.

Note: We are experts at building products that meet our customer's exact requirements. Contact Simplex if your job specifications require additional options or considerations.

This website stores cookies on your computer. These cookies are used to collect information about how you interact with our website and allow us to remember you. We use this information in order to improve and customize your browsing experience and for analytics and metrics about our visitors both on this website and other media. To find out more about the cookies we use, see our Privacy Policy.