Stationary
Saturn
1500KW
1800KW
2000KW
2500KW
3000KW

|
Saturn
Load Bank
The Saturn Load Bank
is a completely self-contained, freestanding unit which includes
all resistive load elements, load control devices, load element
branch circuit fuse protection, main load bus and terminals,
cooling system, control power supply, unit controller and malfunction
detection system and NEMA type enclosure.
The Saturn pictured at right is an indoor configuration. An
exhaust hood is required for exterior use.
Ultra-high capacity load testing of generators or electric dynamometer
testing of large engines and turbines is achieved with the Simplex
Saturn Load Bank. The unit capacity range of the Saturn
is 1500-3000KW, resistive, unity power factor. Saturns may be
used singly or in systems of multiple units which yield total
capacities of tens or hundreds of megawatts.
The Saturn is a single or dual voltage Load Bank suitable
for all common 60 and 50 Hertz voltages up to 600V. Loads are
stepped in any increment of 50KW, or, optionally, in fixed steps
to 5KW or infinitely variable.
Cooling System: Using an ultra high volume forced air
cooling system, up to 60,000CFM for the 3000KW Saturn, air temperature
rise is limited to that seen in smaller Load Banks, in the 150-200°F
range.
Load Control: Master load toggle switch and load step
toggle switches
|
Simplex Load Banks can
be used to satisfy the requirements of the National Fire Protection
Association (NFPA) for emergency stand-by power systems. |
|

Features
Self-contained load
and control system
Utilizes the UL Recognized, Powr-Web load element
Branch circuit fuse protection of load elements
Color coded and numbered wiring; power wiring 150°C
Plated bus bar
Benefits
Modular enclosure design with separate and isolated control and
power sections
NEMA-3R, oversize control section with generous cable connection
space
Vertical airflow, exhausts hot air above level of personnel and
away from buildings, pavement etc.
Comprehensive overload, short circuit and malfunction protection
Slide-out, tray mounted load elements
Highly standardized, based upon extensive product line spanning
from 5KW to 3MW |
GENERAL SPECIFICATIONS
Capacity
1500KW, 1800KW,
2000KW, 2500KW,
3000KW; Resistive, 1.0 power factor
Voltage
All common
3-phase
60 and 50 Hz voltages:
60 Hertz: 208V, 220V, 240V, 416V, 440V, 450V, 460V, 480V,
575V, 600V
50 Hertz: 190V, 200V, 208V, 380V, 400V, 416V
Frequency
50, 60 Hertz
Load Steps
50 KW resolution
standard
1-5-10-25KW resolution available
Fan/Control
Internal,
from load bus. Control circuits at 120V via transformer. The
cooling fan operates at 3-phase line voltage. Load control circuits
and fan motor control operate at 120V. Control circuits are fused.
Control circuit fuses are 100,000 A.I.C., 600V rated. External,
480/240V, supply for humidity controller, when ordered.
Cooling
1500-1800KW:
40,000 CFM
1800-2000KW: 50,000 CFM
2500-3000KW: 60,000 CFM
Duty Cycle
Continuous
Sales
Bulletin
Dimensions
and Key Features Diagram
Stationary Load Banks:
Applications and General Specifications,
Features and Options, and Engineers
Specifications
|
|
|
|
Powr-Web Load
Element

Simplex Load Banks utilize the
UL Recognized, Powr-Web load element. The Powr-Web
is an advanced design, air-cooled power resistor specifically
designed for application to load bank systems. The Powr-Web
is conservatively operated at half the maximum temperature rating
of the alloy and features a short-circuit-safe design based on
continuous mechanical support of the resistor by high temperature,
ceramic clad stainless steel rods. The Power Webs
are assembled into discrete trays which are assembled in a vertical
stack. Each tray in the stack is independently
serviceable without disturbing adjacent trays.
 |
Ratings
3333W at 120V
4170W at 139V
8333 watt 240/480V
16,777 watt at 480V
Specifications
Alloy: FeCrAl
Max. continuous temp. rating: 1920°F
Maximum operating temperature as applied in Load Bank: 1080°
F
Cool down time from operating to ambient temperature: 10 seconds

Construction
Calibrated to specific
ohm value
Welded lugs on each end
All load elements are continuously supported by vibration resistant,
ceramic clad, stainless steel throughrods |
Branch Circuit Fuse Protection
The load of a Resistive Load
Bank consists of a dense array of open, uninsulated power resistors
mounted within a cooling air stream. Since the elements are electrically
live, it is possible for a foreign object to penetrate the element
array and create a short circuit of adjacent elements or a short
to ground. Since the elements are densely packed, it is possible
for a short circuit, once started, to rapidly propagate through
the entire element array. As a Load Bank represents a relatively
large amount of power concentrated within a relatively small
volume, a self-propagating, cascading short circuit would have
catastrophic results.
Simplex virtually eliminates
the dangers of short circuit through the use of branch circuit
fuse protection of the load elements. Per NEC 110-10, protective
devices shall clear a fault without extensive damage
to the circuit components. A Simplex Load Bank is divided into
branch circuits of not more than 50 KW each.
|
|
|
Load Elements
Simplex Powr-Web open wire, helically wound, chromium
alloy, thermally derated to 60%. 5% tolerance, 2% balance, .995
p.f.
UL Recognized.
Load Control
Branch circuit contactors, each 50 KW step. Contactors have enclosed
silver surfaced contacts, 120V coils; electrically operated and
electrically held.
Element Circuit Protection
Branch circuit fuses, each 50KW branch circuit, 70A, 200kAIC,
current limiting type.
Temperature
Maximum ambient temperature: 125°F
Exhaust rise: RISE = KW X 3000/CFM (note: as airflow is not laminar,
exhaust air temperatures are not equal at all points at the plane
of air exhaust. Some parcels of air may reach approximately 575°F
before mixing.)
System Protection
Fan failure, high exhaust temperature, high intake temperature;
lockout and alarm.
|
Enclosure
Modular enclosure consists of three parts:
1. NEMA-3R rainproof power section including load elements and
cooling fan
2. NEMA-3R control section, thermally and electrically isolated
from power section
3. Exhaust hood. Mounts atop power section. Vertical flow with
rain separators. Hood may be deleted and a duct flange provided
for indoor applications where air is exhausted through a duct
to the outdoors.
All panels for access to serviceable components are hinged doors
with stainless steel hinges and lockable latches. All exterior
fasteners are stainless steel.
The Load Bank enclosure is of double wall construction for cool
exterior and thermal isolation of the load elements. Cooling
airflow through the enclosure is vertical with cold air intake
at the bottom and hot air exhaust out the top. Intake and exhaust
openings are screened. All parts of the enclosure are abrasive
blasted or chemically etched, primed and finished with a color
as specified. The exhaust hood which is exposed to high air temperatures
is unpainted galvanized steel.
|

Power Wiring
150°C insulated; color coded.
Control Wiring
105°C, color coded and/or numbered.
Power Connection
Plated bus bar within an oversize terminal junction box.
 |