Water
Cooled
LBW-Series
50KW-2500KW

|
 |
GENERAL SPECIFICATIONS
Capacity
50KW-2500KW,
Resistive, 1.0 p.f.
Greater than 2500KW available as multiple modules.
Voltage
3-Phase, 3-Wire;
208V, 220V, 240V, 380V, 416V, 460V, 480V to 250VDC
Frequency
50Hz, 60Hz
and 400Hz
Load Steps
25KW, 50KW,
100KW
Coolant
City water,
closed -loop heat exchanger, natural water (river, lake, etc.)
brine*, sea-water*
*Requires optional nickel alloy construction elements.
Cooling Characteristics
Normal
Duty
10 GPM per 100KW, 62.5°F rise
Minimum Cooling Requirements
6.25 GPM per 100KW, 100°F rise, outlet not to exceed 170°F
Special Duty, Chilled Water Systems
50 GPM per 100KW, 12.5°F rise
Coolant Requirements
KW = GPM x Temp. Rise (F) x .16
GPM = KW / (Temp. Rise x .16)
Temp. Rise (F) = KW / (GPM x .16)
Particles must be less than 150 microns or a filter is required
Pressure Drop
5 PSI or less
Control Power
Internal or
external source, transformer isolated, 120V
Pressure
180PSI, optional
to 1500 PSI
Duty Cycle
Continuous
Dimensions
and Key Features Diagram
|
Features
Load Elements
Water-immersion
type, screw-plug mounting
Water Connections
2", 4", or 6" as required by flow
Coolant Flow Control
Main electrically operated valve
Load Element Circuit Protection
Branch circuit fuses, each 50KW branch
600V, 200KAIC branch circuit fuses
Power Wiring
150°C insulated
Power Connection
Bus bar
System Protection
Sensed at each load cell: overpressure, overtemperature,
low coolant level, loss-of-flow. Lockout and alarm at control
panel.
Controller
Simplex D-Series Digital Load Bank Controller: PLC based control
system with color - TFT LCD touchpanel operator interface with
bright colors, excellent contrast and wide viewing angle, perfect
for bright sunlight or low light conditions. Network capable
(MODBUS RTU over RS-485 or Ethernet) to integrate digital power
meters, data outputs from generator controllers, thermocouple
inputs, and to integrate single or multiple control stations.
The D-Series will also integrate to a PC or can be assigned an
IP address for remote access. |
Overview
Water-cooled Load Bank
System
50-2500KW, to 600VAC, to 250VDC
Compact, space-efficient design
Totally quiet operation
Suitable for use with chilled-water systems
Digital control
Description
The Simplex LBW-Series comprises
a line of water-cooled Load Banks, 50-2500KW, to 600VAC, 250VDC.
The LBW-Series is an attractive alternative to air-cooled Load
Banks: it is perfectly quiet and cool running; it is extremely
compact and may be installed in otherwise unutilized space; it
is virtually maintenance free.
The LBW-Series is more reliable and maintenance free than a comparable
air-cooled Load Bank due to two principle factors:
1. The water-cooled unit can be installed indoors in a controlled
environment versus an outdoor installation which is exposed to
the elements.
2. The water-cooled Load Bank operates at much lower temperatures
than an air-cooled unit.
Although high in unit cost than a comparable air-cooled Load
Bank, the water-cooled unit can be significantly less costly
to install. The water-cooled unit may require far less connection
cable/conduit since it can be installed indoors, possibly nearer
to the power source.
The LBW-Series is ideal for installation in buildings in central-city
areas, industrial parks or office complexes where an outdoor
air-cooled Load Bank would be architecturally obtrusive or impossible
to install due to space restrictions.
The LBW-Series consists of an assembly of high-pressure load
cells in a structural steel tubing frame, clad with steel panels.
Coolant flow is via intake and exhaust manifolds with feeder
lines to each load cell. Coolant flow is controlled by a main
electrically operated valve.
The load cells are rated for operating pressures up to 180PSI.
High pressure systems are available. Each load cell includes
sensors for overtemperature, overpressure, loss-of-flow, and
low coolant level. |

Load elements are water immersion power resistors. Discrete,
branch circuit elements with screw plugs are utilized to permit
replacement of individual elements.
Load control is via magnetic contactors. Available load step
ratings are 25KW, 50KW, or 100KW.
Comprehensive branch circuit fusing of load elements is provided.
Each 50KW branch circuit is individually protected by current-limiting
type fuses.
Control power for the Load Bank is provided by 120V, transformer
isolated, internal power supplies. Control power can be derived
internally, from the connected power source or from an external
source.
Power distribution within the Load Bank is via a 3-phase main
copper load bus. Field power connections are made to the bus.
The LBW-Series is suitable for use with a variety of cooling
media, including city water (nominal 50PSI), closed loop chilled
water systems, heat exchanger systems, pumped water from natural
sources (lake, river, etc.) or brine or sea water (requires optional
nickel alloy construction and elements).
Limited temperature rise-high flow rate systems are available
for use with chilled water systems. These Load Banks limit temperature
rise to a nominal 12.5°F and consequently accept very high
flow rates (50 GPM per 100KW). |