LBD-Series |
|
||||||||||||||||||||||||||||||||||||||||||||||||||
Simplex LBD-Series Load Banks are intended for use with water cooled engine generator sets equipped with unit mounted radiators. The essential consideration for installation is that it be located somewhere within the radiator air outflow. Installation is simple and adaptive to site/system conditions in numerous ways, including direct bolted attachment to the radiator, mounting within an air duct, wall mounting over the air outflow opening, indoors or outdoors. Since the design is adaptive to varying site conditions, Simplex LBD-Series Load Banks are ideal for after market retrofit. Many options are available to suit individual requirements and simplify installation. LBD-Series Load Banks are of a modular-building block design. Simplex builds them up from stock modular parts to match your radiator or duct dimensions exactly. The control section's standard location is on the left side, but it may be ordered on the right side. A control section may be required on both sides in some applications. |
![]() Features This product has earned the UL Listing Mark Utilizes the UL Recognized Powr Rod load element Branch circuit fuse protection of load elements Magnetic contactor control of load Multiple step load configurations 150°C XLP insulated power wiring Power terminal block with standard size pressure terminals for common building wire Local or remote control available Manual or automatic control available 120V control circuits Install at any point within radiator air outflow Install indoors or outdoors (via option modification) Many installation accessories available Galvanized steel construction Automatic over temperature protection Control components separate and isolated from load elements Continuous duty |
Reliability Exercise and testing of standby generator sets to assure readiness and eliminate the negative effects of both prolonged standby and of no-load exercise. Base load leveling to eliminate the deleterious effects of low load operation: manual application or fully automatic in response to dynamic load demand. Automatic protection against generator reverse power and motoring of prime mover by power regenerated by inertial loads. Options Mounting Angles Mounting Feet Nema-3R Modification Automatic Current Sensing Operation VM-AM-FM Meters with switches KW Meter Cooldown Timer Auto-Exercise Anti-Condensation Heaters |
|||||||||||||||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
Total Width = Opening Width + 2" + Control Section(s) Width 10" x 24" Control Section = 19.355" W 20" x 24" Control Section = 11.355" W 20" x 48" Control Section = 13.355" W Note: A Control Section may be required on both sides for some applications. Due to system complexity, actual dimensions may vary. |
![]() Remote Control Panel 15" W x 15" H x 10" D 24" W x 24" H x 12" D |
||||||||||||||||||||||||||||||||||||||||||||||||||
|
![]() Features Totally enclosed element, eliminates shock hazard Sealed, unaffected by weather and airborne oil/dirt Rugged metallic housing unaffected by vibration Requires no cool down Long life, rustproof UL Recognized Component |
|
|||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
|||
![]() |
|||
(Engine Radiator Airflow Cooled) |
|||
1. Generator Load Bank 1.1 General: An engine radiator airflow cooled, resistive Load Bank is required for permanent, on site installation as a component of a standby engine generator system. The Load Bank shall be designed for (remote, local), (automatic, manual) control. The Load Bank shall bear the listing mark of Underwriters Laboratories (UL Listing). 1.2 Installation: The Load Bank shall be installed within the air outflow of the engine unit mounted radiator and shall be cooled by the radiator airflow. The Load Bank may be installed by one of the following methods: 1.2.1 Bolted attachment to radiator with duct and flex coupling to air outlet in wall. 1.2.2 Installation within air duct; flex transition to radiator and solid duct transition to air outlet in wall. 1.2.3 Bolted attachment to interior wall with duct and flex coupling to radiator. 1.2.4 Bolted attachment to exterior wall over air outlet. Load Bank should be weatherproof for this installation. 1.3 Electrical Connection: Power source to Load Bank connection is 3-phase, 3-wire plus ground. Additional control wire connections for remote control as required. 1.4 Load Bank Rating: 1.4.1 Capacity: _____ KW, 1.0 p.f. 1.4.2 Load Steps (5, 10, 20, 25, 40, 50) KW load step resolution 1.4.3 Voltage: _____V AC, 3-ph., 3-W 1.4.4 Frequency: (50, 60, 400) Hertz 1.4.5 Air intake temperature: 155°F max (radiator air outflow) 1.4.6 Airflow requirements: Radiator air outflow 1.4.7 Duty Cycle: Continuous 1.4-8 Air temp. rise: 100°F, nominal 1.4.9 Air back pressure: .25-.50" water column 1.5 Load Bank Design 1.5.1 General: The Load Bank shall be a completely self-contained unit which includes all resistive load elements, load control devices, load element branch circuit fuse protection, main load bus and terminals, control terminals, system protection devices and NEMA enclosure of required type. 1.5.2 The Load Bank shall be the manufacturer's standard product that has been investigated, tested and listed by Underwriters Laboratories as a system for the purpose intended. Simple assemblies of listed parts that are not system UL listed shall not be acceptable. |
1.5.4 Load elements: Load elements shall be UL listed, labeled or recognized, totally enclosed, sealed and weatherproof with an electrically grounded outer sheath such that the element can not be electrically short-circuited by external foreign objects and personnel are protected against accidental electrical shock. Elements shall be individually replaceable. Open wire type elements in which the electrically live conductors are exposed and which can be short circuited to each other or to ground by foreign objects or by the breakage of an element or an element support shall not be permitted. 1.5.5 Load element short circuit protection: Branch circuit fuses, per each 50KW load branch circuit. Fuses shall be 200,000 A.I.C current limiting type. 1.5.6 Load control: One magnetic contactor per each fused branch circuit. 1.5.7 Load Bank power wiring shall be 150°C XLP insulated. 1.5.8 Main terminals: Barrier type power terminal block with compression type terminal to accept stranded building wire. Provide chassis ground stud with compression type terminal. 1.5.9 Control wiring shall be 105°C XLP insulated. 1.5.10 Control power shall be derived internally from the main load bus. Control and protective circuits shall operate at 120V via control power transformer or line-neutral circuit and shall be fused. 1.5.11 System protection: The Load Bank shall include a comprehensive protection system to protect against overheating. The system shall function to disconnect the load elements from the power source and activate an alarm upon sensing an exhaust air temperature greater than 300°F. 1.6 (Local, Remote) Control Panel 1.6.1 A NEMA (1,3R) control panel for (automatic, manual) operation shall be provided. The panel shall include: 1.6.2 Control power on-off pushbuttons 1.6.3 Normal operation indicator lamp 1.6.4 Master load control switch 1.6.5 Load step control switches 1.6.6 Cooling failure alarm indicator lamp 1.6.7 Remote control panel shall be UL listed. |
1.8 Start-up Service: The Load Bank manufacturer is to provide one day start-up service of the Load Bank, on site, after the Load Bank has been installed and connected. 1.9 Qualifications of Load Bank Manufacturer 1.9.1 The Load Bank shall be a product of a firm regularly engaged in the design and manufacture of generator Load Banks. 1.9.2 The Load Bank manufacturer shall demonstrate at least five years experience with at least twenty-five successful installations of Load Banks similar or equal to the Load Bank specified herein. 1.9.3 The Load Bank for this application shall be a Simplex LBD-Series as manufactured by Simplex, Inc. 1139 N. MacArthur Blvd., Springfield, Illinois 62702, 800-637-8603 Add the following section to provide for Load Bank operation as an automatic load regulator to maintain a preset load level. 1.10 Automatic Load Bank Controller 1.10.1 The Load Bank is to be equipped with an automatic controller which will be activated when the Load Bank mode control selector switch is placed in the automatic position. 1.10.2 In automatic mode, the Load Bank is to be on-line and continuously operative whenever the power source runs. The Load Bank shall provide a component of the total power source load and shall be automatically variable in response to dynamic total load demands upon the power source. 1.10.3 The automatic controller shall include control logic, solid-state sensors and time delays which shall act to apply/remove Load Bank component in multiple steps in response to dynamic output of the power source. 1.10.4 The automatic controller shall function to maintain total load upon the power source within a preset bandwidth by adding Load Bank load component as external load component drops and removing Load Bank component as external load rises. 1.10.5 The automatic controller shall sense load (amperes, kilowatts). 1.10.6 Full manual control of the Load Bank shall be restored when the mode selector switch is placed in the manual position. 1.10.7 The automatic controller shall include a solid-state load sensor with level and time delay adjustment and output contacts for each load step. A current transformer for external installation shall be provided. |
|