SIMPLEX
TANK FILLING SYSTEMS OPTIONS
FP = FuelPort (A1 Full-Size only), AFP =
Automatic FuelPort, SP = SmartPump
A = Available, NA = Not Available, S = Standard
|
|
NO. |
FP |
AFP |
SP |
DESCRIPTION |
|
020 |
A |
A |
A |
2" fire rated shutoff valve
assembly for installation on AST fuel inlet, consisting of fire
rated ball valve and self-closing fusible link valve |
|
022 |
A |
A |
A |
3" fire rated shutoff valve
assembly for installation on AST fuel inlet, consisting of fire
rated ball valve and self-closing fusible link valve |
|
030 |
A1 |
A |
A |
2" dry disconnect adaptor
installed on inlet in lieu of standard part B coupler |
|
035 |
A1 |
A |
A |
3" dry disconnect adaptor
installed on inlet in lieu of standard part B coupler |
|
045 |
A1 |
A |
NA |
2" fuel strainer, Y-type,
cast iron, 20-mesh stainless steel screen, installed |
|
047 |
NA |
A |
A |
3" fuel strainer, Y-type,
cast iron, -032" stainless steel screen, installed |
|
051 |
NA |
A |
A |
Tank leak sensor float switch type,
for mounting in a vertical position in collection sumps, monitoring
pipes and steel double wall tank sumps. Included in controller:
tank leak alarm, tank fill shutoff, alarm contacts. For installation
in 2" fitting. |
|
052 |
NA |
A |
A |
Tank leak sensor optical type,
for mounting in a vertical position in collection sumps, monitoring
pipes and steel double wall tank sumps. Included in controller:
tank leak alarm, tank fill shutoff, alarm contacts. For installation
in 2" fitting. |
|
058 |
NA |
A |
A |
Digital level indicator scaled
in percent level. Not available for gasoline versions, use #059.
Level transmitter supplied for field installation in 2"
tank fitting. |
|
059 |
A |
A |
A |
Hydrostatic level gauge, hand pump
type with 5" dial type indicator calibrated in gallons.
Transmitter installed in 2" tank fitting. Supplied in lieu
of standard digital level indicator with oil AFP. |
|
075 |
A |
NA |
NA |
Flush Wall-mounting bracket for
2" or 3" |
|
076 |
A |
NA |
NA |
Flush Wall-mounting bracket for
4" |
|
085 |
A |
NA |
NA |
3" post assembly with base.
48" high, w/clamps |
|
086 |
A |
NA |
NA |
3" post clamps |
|
088d |
A |
A |
A |
2" fire rated shutoff valve
in lieu of bronze valve |
|
088e |
A |
A |
A |
3" fire rated shutoff valve
in lieu of bronze valve |
|
093b |
A |
A |
A |
2" fusible link fire valve
on outlet |
|
093c |
A |
A |
A |
3" fusible link fire valve
on outlet |
|
182 |
NA |
NA |
A |
Full enclosure for SmartPump. Lockable,
with containment basin and hand pump. |
|
509 |
NA |
A |
S |
Control power transformer for 240/480v
service |